UL Listed T TypeWater Flow Detector With Retard

UL Listed T TypeWater Flow Detector With Retard

Precautions

The flow indicator should be installed on a tee with a 1-inch NPT branch pipe, including branch pipe sizes of 1 inch, 1¼ inch, 1½ inch, and 2 inches, as specified in the drawings and/or this document. The flow indicator should be installed on any standard-sized clear pipe section, whether horizontal or vertical. The indicator's sensitivity ranges from 4 to 10 gallons per minute, with a static pressure rating up to 450 psi (for 1-inch to 2-inch (ON25 - DN50) pipe). The indicator should respond to flow in a specified direction after a preset delay, which is field-adjustable. The delay device should be a sealed mechanical-pneumatic mechanism with a visually adjustable delay adjustment. Note: The cover is made of aluminum; a plastic cover is also acceptable.

Technical Specification

Working Pressure:Max3.1Mpa (450psi)
Sensitivity:15.0-37.5L/min (4-10GPM)
Contact Rating:Two sets of SPDT (Form C);10.1A@125/250VAC;2A@24VDC
Enclosure Rating:NEMA 4- suitable for indoor/outdoor
Compatible Pipe :Steel pipe, schedule 10 through 40
Operating Temperature: 4.5°C - 49°C (40%F - 120°F)
Maximum Surge:5.5m/s (18FPS)
Retard Structure:Time delay adjustment via rotate dial
Two sets Micro-switch:100% synchronization
Tamper Device :Special tamper screws to prevent disassembly
Standards:GB5135.7-2018 &FM1042-2016&UL346

Typical Electrical Connections and Time Delay Adjustment

Dimension

DN INCH W (mm) H (mm) D (Depth) (mm)
25 1" Apr-95 169/7 Feb-54
32 1¼" Apr-95 177/7 Feb-63
40 1½" Apr-95 184/7 Mar-69
50 2" Apr-95 197/8 Mar-82

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 