Select Page

Product Categories

Carbon Monoxide And Heat-Sensing Combined Fire Detection Device

Carbon Monoxide And Heat-Sensing Combined Fire Detection Device

ESF-EI9102

Carbon Monoxide And Heat-Sensing Combined Fire Detection Device

Features

1.Employs non-polar dual-bus technology for simple installation and maintenance;
2.Low power consumption design, resulting in low monitoring and alarm currents;
3.Utilizes temperature compensation technology, minimizing the impact of temperature on gas concentration acquisition;
4.Features valve action feedback information reception; the valve drive function uses a bus power supply, eliminating the need for a separate 24V power supply;
5.Includes automatic sensor fault detection, effectively preventing missed alarms;
6.Ultra-thin design with a simple and compact appearance.

Technical Parameter

Communication Method Non-polar dual-bus
Encoding Method Electronic encoding, address range 1~250
Detection Type Temperature/Carbon Monoxide
Temperature Sensing Category Class B
Operating Voltage Bus 24V (15V~28V pulse voltage)
Monitoring Current ≤500μA
Alarm Current ≤1mA
Valve Actuation One set of DC24V active pulse output/rated current 1.2A, action time 60ms
Gas Sensor Principle CO: Electrochemical
Measuring Range Gas testing range: 0~1000ppm; Temperature measurement range: -20℃~105℃
Measuring Accuracy CO: <±5%FS; Temperature: ±1℃
Alarm Setpoint CO: 190ppm/Temperature: 69℃ (factory preset, can be modified via bus, supports multi-level alarm)
Response Time T90≤60S
Warm-up Time Recommended 5 minutes
Sensor Lifespan 10 years (typical value, under certain operating conditions)
Operating Environment Temperature: -10℃~+55℃; Humidity: ≤95%RH, non-condensing
Dimensions 82mm×68mm×22mm (L×W×H)
Weight 15g

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 