UL Listed V Type Water Flow Detector With Retard
UL Listed V Type Water Flow Detector With Retard
Precautions
The flow indicator should be installed on the system piping as shown in the drawings and/or as specified in this document. The flow indicator should be installed on any standard-sized clear pipe section, whether horizontal or vertical. The indicator's sensitivity ranges from 4 to 10 gallons per minute, with a static pressure rating up to 45 psi (suitable for 2-inch to 8-inch (50 mm to 200 mm) pipe). The indicator should respond to flow in the specified direction after a preset time (field adjustable). The delay mechanism should be a sealed mechanical-pneumatic device with a visible time delay adjustment. Note: The cover is made of aluminum; a plastic cover is optional.
Technical Specification
Working Pressure:Max3.1Mpa (450psi-FM);Max2.1Mpa (300psi-UL)
Sensitivity:15.0-37.5L/min (4-10GPM)
Contact Rating:Two sets of SPDT (Form C);10.1A@125/250VAC;2A@24VDC
Enclosure Rating:NEMA 4- suitable for indoor/outdoor
Compatible Pipe :Steel pipe, schedule 10 through 40
Operating Temperature: 4.5°C - 49°C (40%F - 120°F)
Maximum Surge:5.5m/s (18FPS)
Retard Structure:Time delay adjustment via rotate dial
Two sets Micro-switch:100% synchronization
Tamper Device :Special tamper screws to prevent disassembly
Standards:GB5135.7-2018 &FM1042-2016&UL346
Typical Electrical Connections and Time Delay Adjustment