Addressable/Conventional Aspirating Smoke Detection System
Model:N-EI8922N/N-EI8924N
Material:ABS
Color:Black/White
N-EI8922N/N-EI8924N Addressable/Conventional Aspirating Smoke Detection System
Features
1.Visualization of smoke content, the intelligent terminal can view the wave form of device smoke content after connecting to the device, intuitively feel thecurrent smoke situation,and make adjustments in a timely manner;
2.Adopting the principle of laser cavity detection,accurate monitoring of smoke particles is
achieved;
3.Multilevel alarm function, divided into five alarm stages,and the parameter values for each stage
can be set according to customer needs;
4.Touch CD screen user display interface(8922/8924)and simple and intuitive operation mode,
which can be connected to our fire alarm controller through two buses;
5.Suitable for energy storage fire protection, high-rise spaces(such as airports, sports halls), warehouses, special places(clean rooms,cold storage), important places(such as computer rooms, libraries),and other places.
Specification
1.Operating temperature:-10℃ -40℃
2.Transportation temperature: -40°C-70℃
3.Storage temperature: -40°C -70°C
4.Working humidity: 5% -95%, no condensation
5.Storage humidity:5%-95%
6.Altitude requirement: 0 m to 4000 m (in an environment of 2000 m to 4000 m, the working temperature decreases by 1 °C for every 200 m increase)
7.Rated working voltage: DC24v (working voltage range:20.4V~26.4V)
8.Maximum working current: 1.3A
9.52 holes, with a protection area of 2000m² 104holes, with a protection area of 4000 m²
10.Sensitivity range: <0.8% obs/m
Filter Level 2
Analyzing a single cavity
11.Number of channels: Dual channels, Four channels
12.Address point: 1 address point
The length of the sampling tube is 200m for both tubes, 100m for a single tube, 400m for four tubes, and 100m for a single tube
13.Sampling tube size: outer diameter 25mm, inner diameter 21mm
14.The number of sampling holes is 26 for single tube, 52 for double tubes, 26 for single tubes, and 104 for four tubes
15.Sampling aperture 2.0mm × 25, 5.0mm (end cap)X 1/per tube
16.Airflow monitoring level 3
17.30000 event records
18.Alarm level:5 grades
19.Continuous speed regulation of inhalation volume
20.Display and operate 7-inch touch screen LED lights
21.Relay output:3 pairs
22.Relay carrying: DC30V 2A max/AC125V0.5 Amax
23.Communication method: Two Bus Rs485
24.Design standard: IEC60950-1
25.MTBF:100000 hours
26.Size:300mmx230mmx115mm(length X height X depth)
27.Weight<4.2kg
28.Installation: Wall mounted
Leave Your Message