Выбрать страницу

Категории продуктов

Aspirating Smoke Detector

Aspirating Smoke Detector

JTY-GX-EI8922/JTY-GX-EI8924

JTY-GX-EI8922N/JTY-GX-EI8924N

Aspirating Smoke Detector

Характеристики

1.Visualized smoke concentration: After connecting to the device via a smart terminal, users can view the smoke concentration waveform for a clear understanding of the current smoke situation and facilitate timely adjustments.
2.Utilizes laser cavity detection technology for accurate smoke particle monitoring.
3.Multi-level alarm function: Divided into five alarm stages, with parameter values ​​for each stage customizable to customer needs.
4.Touchscreen LCD user interface (8922/8924) and simple, intuitive operation mode; connects to our fire alarm controller via a two-wire bus.
5.Suitable for energy storage fire protection, large spaces (such as airports and stadiums), warehouses, special locations (cleanrooms, cold storage), and important locations (such as computer rooms and libraries).

Technical Parameter

Product Model JTY-GX-E18922 JTY-GX-E18922N JTY-GX-E18924 JTY-GX-E18924N
Environmental Characteristics Operating Temperature -10°C to 40°C
Transport Temperature -40°C to 70°C
Storage Temperature -40°C to 70°C
Operating Humidity 5%-95%, non-condensing
Storage Humidity 5%-95%
Altitude Requirement 0 m to 4000 m (In environments between 2000 m and 4000 m, the operating temperature decreases by 1°C for every 200 m increase in altitude)
Power Supply Parameters Input Voltage Rated operating voltage: DC24V (Operating voltage range: 20.4V~26.4V)
Operating Current Maximum operating current: 1.3A
Host Parameters Protection Area The entire unit has 52 holes, providing a protection area of 2000m² The entire unit has 104 holes, providing a protection area of 4000m²
Sensitivity Range ≤0.8%obs/m (refer to national standard GB15631-2008)
Filtering 2-stage filtration
Analysis Chamber Single chamber
Number of Channels Dual channel Four channel
Address Points 1 address point
Sampling Tube Length Total length of dual-tube: 200m; maximum length of single-tube: 100m Total length of four-tube: 400m; maximum length of single-tube: 100m
Sampling Tube Size Outer diameter: 25mm; Inner diameter: 21mm
Number of Sampling Holes 26 single-tube holes, 52 dual-tube holes in total 26 single-tube holes, 104 four-tube holes in total
Sampling Hole Diameter 2.0mm x 25, 5.0mm (end cap) x 1/tube
Airflow Monitoring 3 levels
Event Log 30,000 pieces
Alarm Levels 5 levels
Intake Volume Stepless speed regulation
Display and Operation 7 o'clock touchscreen LED lights 7 o'clock touchscreen LED lights
Relay Output 3 pairs
Relay Carrier DC30V 2Amax/AC125V 0.5Amax
Communication Method Dual bus, RS485
Other Parameters Safety Design IEC60950-1
MTBF 100,000 hours
Размеры 300mm×230mm×115mm (L×H×D)
Weight <4.2kg
Installation Method Wall-mounted installation
Heat Dissipation Method Natural heat dissipation
Execution Standards GB15631-2008

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Оставьте свое сообщение