Fine Water Mist Fire Extinguishing Device

Description
1.The high pressure water mist system device uses water as the fire extinguishing medium, and uses a special atomizing nozzle to decompose the water flow into small water droplets to extinguish the fire under a specific pressure (usually the minimum pressure of the nozzle is 10MPa). With the characteristics of economy and wide application, it has become an important technology to replace the halon fire extinguishing system, and has a wide application prospect.
2.Fine water mist: sprayed at the minimum working pressure of the nozzle, measured on a plane 1m down from the axis of the nozzle, the water mist with the droplet size Dv0.99 less than 400μm, and Dv0.50 less than 200μm.
Composition and working principle
The water mist fire extinguishing device consists of a high-pressure water mist special water storage tank, a water mist fire extinguishing device pump unit (including high-pressure main pump, high-pressure backup pump, voltage stabilizer pump, pump unit control cabinet, water inlet solenoid valve, water inlet filter It is composed of water supply system, water supply pipe network, partition control valve box group of water mist fire extinguishing device, water mist sprinkler, high pressure water mist pipeline and fire detection and alarm system. It works as follows:

Model and technical parameters
Модель |
Flow rate L/min |
Pressure MPa |
Nozzle pressure MPa |
System power kW |
Температура ℃ |
standard |
System type |
XSWBG 115/14 BA |
115 |
14 |
≥10 |
40 |
4~50 |
XF1149-2014 |
Pump group high pressure open water mist fire extinguishing device |
XSWBG 230/14 BA |
230 |
70 |
XSWBG 345/14 BA |
345 |
100 |
XSWBG 460/14 BA |
460 |
130 |
XSWBG 575/14 BA |
575 |
160 |
XSWBG 690/14 BA |
690 |
190 |
XSWBG 805/14 BA |
805 |
220 |
Device installation
Модель |
Minimum size of pump room |
Pump room installation layout |
Water supply requirements (choose one of two) |
System Drainage Requirements |
System power |
Hoisting equipment |
Fire fighting pool |
Municipal water supply |
XSWBG 115/14 BA |
Area>20m2
Height>3m
Or provide the size to confirm the design by the manufacturer |
200mm high cement whole board foundation, arranged according to the actual situation on site; or designed by the manufacturer |
Not less than the water consumption for one fire extinguishing |
Two independent municipal slave water; each flow is not less than the small rated system flow |
≥200L/min |
Two independent dual power supply AC380V |
5T forklift or equivalent lifting capacity lifting equipment |
XSWBG 230/14 BA |
XSWBG 345/14 BA |
XSWBG 460/14 BA |
XSWBG 575/14 BA |
XSWBG 690/14 BA |
XSWBG 805/14 BA |
Zone control valve
Item |
Parameters |
Item |
Parameters |
Diameter |
DN15~DN50 |
Electric Actuator |
Voltage |
AC220V |
Рабочее давление |
14MPa |
Мощность |
15W |
Medium |
living water |
opening time |
30s |
Температура |
(4~50)℃ |
Protection class |
IP65 |
Pressure range |
(8~14)MPa |
Other functions |
with manual |
Open type nozzle
Модель |
Connection size |
Flow Coefficient |
Minimum working pressure МПа |
maximum working pressure МПа |
droplet diameter DV0.9
мкм |
XSW-T 0.5/10 BA |
M18X1.5 |
0.5 |
10 |
14 |
≤90 |
XSW-T 0.7/10 BA |
0.7 |
XSW-T 1.0/10 BA |
1.0 |
XSW-T 1.2/10 BA |
1.2 |
XSW-T 1.5/10 BA |
1.5 |
XSW-T 2.0/10 BA |
2.0 |
XSW-T 2.5/10 BA |
2.5 |