Hydrogen, Carbon Monoxide, And Smoke And Heat Combined Fire Detection Device
ESF-EI9105

Caraterísticas
1.Employs non-polar dual-bus technology for simple installation and maintenance;
2.Low power consumption design, resulting in low monitoring and alarm currents;
3.Utilizes temperature compensation technology, minimizing the impact of temperature on gas concentration acquisition;
4.Features valve action feedback information reception function; valve drive function uses bus power supply, eliminating the need for a separate 24V power supply;
5.Features automatic sensor fault detection function, effectively preventing missed alarms;
6.Ultra-thin design with a simple and compact appearance.
Technical Parameter
| Communication Method |
Non-polar dual-bus |
| Encoding Method |
Electronic encoding, address range 1~250 |
| Detection Type |
Smoke/Temperature/CO/H2 |
| Temperature Sensing Category |
Class B |
| Operating Voltage |
Bus 24V (15V~28V pulse voltage) |
| Monitoring Current |
≤5mA |
| Alarm Current |
≤7mA |
| Valve Actuation |
One set of DC24V active pulse output/rated current 1.2A, action time 60ms |
| Gas Sensor Principle |
CO: electrochemistry; H2: metal oxide semiconductor |
| Measuring Range |
CO testing range: 0~1000ppm; Temperature measurement range: -20°C~105°C; H2 measurement range: 0~1000ppm |
| Measuring Accuracy |
CO: <±5%FS; Temperature: ±1℃ |
| Alarm Setpoint |
CO: 190ppm / Temperature: 69℃ / Smoke: Factory preset / H2: 200ppm (can be modified via bus, supports multi-level alarms) |
| Response Time |
T90≤60S |
| Warm-up Time |
Recommended 5 minutes |
| Sensor Lifespan |
5 years (typical value, under certain operating conditions) |
| Operating Environment |
Temperature: -10℃~+55℃; Humidity: ≤95%RH, non-condensing |
| Dimensões |
82mm×68mm×22mm (L×W×H) |
| Weight |
15g |