The foam closed system is a foam water sprinkler system with a closed sprinkler. The sprinkler is equipped with a thermosensitive element (glass ball or fusible alloy), which is usually closed. Only when the temperature of the fire area reaches the set value can the foam mixture be sprayed. The system has both foam extinguishing and water spray cooling functions, which can precisely extinguish the fire at the point of ignition. It is a “local response” fire extinguishing system.
Core components
Closed nozzle: special nozzle with thermal sensor, divided into standard type and foam special type, with operating temperature of 68 ° C, 93 ° C or 141 ° C
Alarm valve group: Wet type alarm valves are commonly used to maintain pressure water in the pipeline network. After the nozzle is activated, the alarm will automatically start and the fire pump will be activated
foam concentrate supply device: including foam concentrate storage tank, capsule and proportioner to ensure that foam concentrate and water are mixed in proportion
Water flow indicator: Each fire compartment is equipped with one to provide feedback on the specific location of the fire area
Pressure switch: linkage start fire pump and foam liquid supply device
Automatic fire alarm system: Some systems can be combined with fire detectors to achieve pre start and improve response speed
Принцип работы
Fire occurrence: The temperature in the ignition area rises to the operating temperature of the closed nozzle thermal sensor
Nozzle opening: The thermal sensor ruptures, the closed nozzle opens, and the pressure inside the pipeline decreases
System startup: the pressure switch of the alarm valve group acts, and the fire pump and foam proportioner are started in linkage
foam injection: the foam mixture is sprayed to the fire area through the open nozzle, and the foam covering suffocation is used to extinguish the fire
Manual cooling: After the fire is extinguished, it can be manually switched to water spray mode to cool the fire area and prevent reignition
System reset: Replace damaged nozzles, drain excess water from the pipeline network, and restore the system to standby mode
Core strengths
Accurate firefighting and efficient utilization of resources
Only the sprinkler in the fire area is opened to avoid waste of water resources and foam liquid caused by whole area spraying
The water flow indicator can accurately provide feedback on the fire area, making it easy for firefighters to quickly locate the fire situation
Low operation and maintenance costs, easy to maintain
The probability of damage to the closed nozzle is low, and only the nozzle after action needs to be replaced, without the need for large-scale maintenance
The pipe network is usually filled with pressure water, and routine maintenance only needs to check the water pressure and the validity period of foam liquid regularly
Wide applicability and strong scene compatibility
Can be used for relatively enclosed small spaces or combined for zoning protection of large buildings
Support the combination of wet, dry, pre action and other spray systems
Reduce secondary losses and protect property safety
Local spray mode can minimize the impact of water stains on property in non fire areas to the greatest extent possible
Suitable for places sensitive to water damage, such as archives, precision instrument rooms, etc
Flexible design and strong customizability
Nozzles with different operating temperatures can be set up according to different locations to meet special environmental requirements
Support strengthening local protection and increasing nozzle density in high-risk areas