Sélectionner une page

Catégories de produits

Hydrogen, Carbon Monoxide, And Smoke And Heat Combined Fire Detection Device

Hydrogen, Carbon Monoxide, And Smoke And Heat Combined Fire Detection Device

ESF-EI9105

Hydrogen, Carbon Monoxide, And Smoke And Heat Combined Fire Detection Device

Caractéristiques

1.Employs non-polar dual-bus technology for simple installation and maintenance;
2.Low power consumption design, resulting in low monitoring and alarm currents;
3.Utilizes temperature compensation technology, minimizing the impact of temperature on gas concentration acquisition;
4.Features valve action feedback information reception function; valve drive function uses bus power supply, eliminating the need for a separate 24V power supply;
5.Features automatic sensor fault detection function, effectively preventing missed alarms;
6.Ultra-thin design with a simple and compact appearance.

Technical Parameter

Communication Method Non-polar dual-bus
Encoding Method Electronic encoding, address range 1~250
Detection Type Smoke/Temperature/CO/H2
Temperature Sensing Category Class B
Operating Voltage Bus 24V (15V~28V pulse voltage)
Monitoring Current ≤5mA
Alarm Current ≤7mA
Valve Actuation One set of DC24V active pulse output/rated current 1.2A, action time 60ms
Gas Sensor Principle CO: electrochemistry; H2: metal oxide semiconductor
Measuring Range CO testing range: 0~1000ppm; Temperature measurement range: -20°C~105°C; H2 measurement range: 0~1000ppm
Measuring Accuracy CO: <±5%FS; Temperature: ±1℃
Alarm Setpoint CO: 190ppm / Temperature: 69℃ / Smoke: Factory preset / H2: 200ppm (can be modified via bus, supports multi-level alarms)
Response Time T90≤60S
Warm-up Time Recommended 5 minutes
Sensor Lifespan 5 years (typical value, under certain operating conditions)
Operating Environment Temperature: -10℃~+55℃; Humidity: ≤95%RH, non-condensing
Dimensions 82mm×68mm×22mm (L×W×H)
Weight 15g

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Laissez votre message