Seleccionar página

Válvula de control del nivel de agua hidráulica H142X-16Q

The H142X-16Q Hydraulic Water Level Control Valve automatically regulates water levels via hydraulic/buoyancy forces, offering overflow and dry-up protection for water supply and industrial systems at max 16 bar and 0°C-80°C.

Más información en Válvula de control ¡Catálogo!

Válvula de control del nivel de agua hidráulica H142X-16Q

ESPECIFICACIÓN DEL MATERIAL
No. Nombre Material No. Nombre Material
1 Tapa de válvulas QT450 6 Through hole   stem Acero inoxidable
2 Control Room QT450 7 Guide fork QT450
3 Primavera SS304 8 Valve disc QT450
4 Piston QT450 9 Cuerpo de la válvula QT450
5 Cuerpo de la válvula QT450

 

DIMENSIONES
Specification(DN) 50 65 80 100 125 150 200 250 300 350 400 450 500 600
Valve length (mm) 200 205 225 245 270 300 350 445 495 555 595 645 745 840
Test pressure (MPa) case 1.5-2.4
seal 1.1-1.76
Presión nominal (MPa) 1.0-1.6
Temperatura aplicable 0-80℃
Medios aplicables Agua y fluidos poco corrosivos

DESCRIPCIÓN DEL PRODUCTO

1.Hydraulic Water Level Control Valve is a valve driven by hydraulic pressure or buoyancy to automatically control the water level in a container, pipe or pool.
2.It is widely used in water supply, drainage, irrigation and industrial circulating water systems.
3.Water level regulation: Automatically open or close the valve according to the preset water level to maintain a stable liquid level (such as a reservoir or water tower).
4.Overflow protection: Quickly close when the water level is too high to prevent overflow from causing water waste or equipment damage.
5.Dry-up protection: Automatically cut off drainage when the water level is too low to avoid idling of the pump or system paralysis.
6.Energy saving and automation: Reduce manual intervention and optimize water resource utilization efficiency.

Requisitos de instalación

1.Horizontal installation to avoid tilting that affects the float or hydraulic feedback sensitivity.
2.Pre-filter to prevent impurities from blocking the valve disc.

Maintenance points

1.Regularly clean the valve body and filter to prevent scale or silt from clogging.
2.Check whether the float is leaking and whether the lever is deformed.
3.Calibrate the water level setting value to ensure the accuracy of the action.

SOLICITUD

1.Municipal water supply: automatic water replenishment and water level control of water towers and high-level water tanks.
2.Drainage system: overflow control of sewage treatment plants and underground garage water collection wells.
3.Agricultural irrigation: timed and quantitative water delivery management of reservoirs and channels.
4.Industrial circulating water: water level maintenance and protection of cooling towers and boiler systems.

PRESIÓN DE TRABAJO

Presión máxima de trabajo 16 bar (230 psi).

ESTÁNDAR

Las pruebas de los productos se realizan de acuerdo con la norma GB/T13927 Prueba de presión de válvulas industriales.

RANGO DE TEMPERATURA

0 °C a 80°C.

REVESTIMIENTO

Revestimiento epoxi unido por fusión.

Válvula de control del nivel de agua hidráulica H142X-16Q Válvula de control del nivel de agua hidráulica H142X-16Q Válvula de control del nivel de agua hidráulica H142X-16Q

Deje su mensaje